Uploading Refrigerated Assets via Template

Uploading Refrigerated Assets via Template

Whenever you need to create multiple refrigerated assets en masse, you can take advantage of the asset import template.

Before you upload assets, make sure you have the required asset types added to Asset Manager as well as /wiki/spaces/UJNK/pages/812549301 loaded to Inventory Manager.


⦿ How to Create Refrigerated Assets via Template
  1. Click the hamburger menu, and select Assets (Equipment) > Imported Assets.
    Asset Manager module located in the hamburger menu
  2. Switch to the Upload Assets section.
  3. Click Excel Template (All Attributes). An Excel file with attributes for all asset types gets downloaded to your device.
    Steps to follow to download a blank template
  4. Find the required asset type, fill out the necessary fields, and save the file.
  5. Click Select .xlxs File (With Custom Attributes), and open the required file. The system starts validating your file.
    1. If errors are found, download the results file, and check the last column to correct the errors. When ready, resubmit the file.
    2. If no errors are found, click Confirm Import.
      Confirming the import of refrigerated assets
  6. Once the file is processed, you are redirected to the Imported Assets section.

Completing the Asset Import Template

Thermometer

What fields should be filled out in the template depends on the asset refrigerant usage type: Rack, Connected To a Rack, Self Contained Asset, or Conventional. To boot, it is also important to check what asset type attributes are marked as required on the asset type details page.

Here is the information you are expected to provide when uploading Refrigerant Assets. This includes information that is used for a Standard Attribute template. Mandatory fields are marked with a red asterisk .

Column headerDefinitionExample
 Refrigerant Usage Type

Your asset may belong to one of the following refrigerant usage types: 

  • Rack
  • Connected To a Rack
  • Self Contained Asset
  • Conventional

Refrigerant Usage Type column in the asset import template

 Rack ID

Identification number of the rack. The field is required only for assets where the Refrigerant Usage Type of the asset type is Rack or Connected To a Rack.

When you connect a refrigerated asset to a rack, enter the tag ID of the rack asset in the Rack id field. Don’t enter the rack ID.

Rack ID column in the asset import template

 Rack Type

Temperature range of the rack. The field is required only for assets where the Refrigerant Usage Type of the asset type is Rack or Connected To a Rack.

One of the following types should be entered:

  • High
  • Low
  • Medium
  • Dual Temp

Rack Type column in the asset import template

 Refrigerant Type

Name of the refrigerant type that your asset uses. The field is required for assets where the Refrigerant Usage Type is Rack and Self Contained Asset.

Refrigerant Type column in the asset import template

✱ Operation Status

Operational status of the asset. Enter one of the available options:

  • INACTIVE Taken out of service completely disconnecting the unit in such a way that it cannot be reactivated without repair.
  • MOTHBALLED The refrigerant has been evacuated from an appliance (or from the affected isolated section or component of an appliance) to at least atmospheric pressure and to temporarily shut down that appliance.
  • NORMAL OPERATION The system is operating at the expected normal procedure.
  • PROVISIONAL OPERATION The system is operating but is subject to change.
  • REMOVE The system has been removed from use completely to be relocated or disposed of.
  • RETROFIT IN PROGRESS The system is currently in the process of being retrofitted.
  • SEASONAL - NON-OPERATION The system is only used when season conditions require the use of the appliance, and it is currently not in operation.
  • SEASONAL - OPERATION The system is only used when season conditions require the use of the appliance, and it is currently in operation.
  • SHUTDOWN The system is turned off and can be turned back on. 
  • UNDER REPAIR The system is currently being fixed.

The field is required for assets where the Refrigerant Usage Type is Rack and Self Contained Asset.

Operation Status column in the asset import template

 Total Charge

The current amount of refrigerant gases contained in the asset. The field is required for assets where the Refrigerant Usage Type is Rack, Self Contained Asset, and Conventional

Total Charge and Capacity must be in Pounds and Decimals (i.e 1.8 pounds = 1 pound 13 ounces). Then the system converts it to Pounds and Ounces.

Total Charge

✱ Vendor

Name of the provider who identified the total charge of the system. Enter the name as it appears across the ServiceChannel platform.

If the required provider isn’t in the SC platform, you can manually enter the required company name.

The field is required for assets where the Refrigerant Usage Type is Rack and Self Contained Asset.

Vendor column in the asset import template

✱ Description

Description of how the initial charge was taken. Possible options: 

  • Calculation: This refers to determining the refrigerant charge based on known system parameters and calculations. This might include using formulas that consider the volume of the system, the type of refrigerant, and other relevant factors.
  • Established: This term indicates a refrigerant charge amount that has been set or confirmed through reliable and consistent methods. It is typically based on historical data, manufacturer specifications, or other authoritative sources.
  • Manufacturer Tag: This is the information provided on the equipment's nameplate by the manufacturer, which includes the recommended refrigerant charge for optimal operation. The manufacturer tag is a reliable source for determining the correct amount of refrigerant.
  • Measurement: This involves directly measuring the amount of refrigerant in the system using appropriate tools and techniques. It provides an accurate assessment of the current refrigerant charge.
  • MFG Info (Established Range): Manufacturing Information (Established Range) refers to the range of acceptable refrigerant charges provided by the manufacturer. This range accounts for variations in system conditions and ensures the equipment operates efficiently within specified parameters.
  • Onsite Documentation: This includes any records or documentation available at the site that detail the refrigerant charge for the asset. It can include service records, maintenance logs, or other relevant documents that provide information on the refrigerant charge.
  • Approximate: This term indicates an estimated refrigerant charge based on observations, experience, or less precise methods. It is not as accurate as a direct measurement but provides a reasonable estimate for operational purposes.

The field is required for assets where the Refrigerant Usage Type is Rack, Self Contained Asset, and Conventional.

Description column in the asset import template

✱ Has Leak Detector

Enter True if your asset has a leak detector installed.

Enter False if the asset has no leak detector.

Has Leak Detector column in the asset import template

Is tracked by CARB

Enter True if your refrigerated or HVAC asset contains ozone depleting gases and meets the requirements to be tracked by the California Air Resources Board (CARB). The asset manufactured date needs to be specified in this case.

Enter False if your asset doesn’t contain that much of refrigerant and isn’t tracked by the CARB.

Is Tracked By CARB column in the asset import template