Refrigerant Leak Settings sets the parameters for when refrigerant or HVAC asset types require maintenance or repair. Having accurate leak settings is necessary to ensure guidelines and protocols are met. When configuring, you can change the:

Refrigerant Leak Settings Page

Note

Please, contact your ServiceChannel representative should you need to change the decimal point (.) to decimal comma (,) on non-monetary amounts, such as: 

  • Hours and Duration 
  • Quantity Amounts 
  • Weight. 


Panel
bgColor#F9F9F9
titleColor#0e3367
titleBGColor#EAEAEA
borderStylenone
title⦿ How to Access Refrigerant Leak Settings
  1. Click the menu icon to expand the list.
    ALP
  2. Select Admin from the list. 
  3. Click Refrigerant Tracking to enter Refrigerant Leak Settings.
    Refrigerant Admin Settings  


Anchor
CreatingRefrigerantLeakSetting
CreatingRefrigerantLeakSetting
Creating Refrigerant Leak Settings

You can create specific requirements for those refrigerant or HVAC asset types based upon the guidelines and protocols for a specific country. In doing so, it provides consistency and precision for monitoring those assets within that country. 


Panel
bgColor#F9F9F9
titleColor#0e3367
titleBGColor#EAEAEA
borderStylenone
title⦿ How to Add a New Requirement
  1. Use the drop-down arrow to select a country.
    Add Country drop-down
  2. Click the add button to start adding refrigerant leak setting. 

Anchor
Leakthreshold
Leakthreshold
Adjusting Leak Threshold

The next part of the process is to set the Leak Rate Threshold for all your refrigerated asset types. The rate that you set must be in compliance with all guidelines and protocols. It is necessary to check your local environmental agency for additional information. The thresholds you set for each of the four types of refrigerated asset types will be the same for all assets in that asset type. When any refrigerant or HVAC equipment is leaking and the leak rate meets or exceeds the specific threshold, Service Automation creates a leak record.

Anchor
Triggerrates
Triggerrates
Trigger Rates

The following Trigger Leak rates applies for a 12-month period. 

Application TypeLeak Rate Effective (1/1/2019)
Industrial Process Refrigeration30%
Commercial Refrigeration 20%
Comfort Cooling10%
All Other Appliances  10%


Anchor
Calculatingmethods
Calculatingmethods
Calculating Methods

EPA outlines four acceptable methods that can be used either individually or in combination to assets full charge:

  1. Equipment manufacturers' determination
  2. Calculations based on component sizes, refrigerant density, volume of piping, and other considerations. 
  3. Actual measurements of the amount of refrigerant added or evaluated from the appliance. 
  4. Use of an established range based on the best available data. This method requires you to document how you determined the full charge. 

The full charge is necessary to determine the leak rate. For commercial refrigeration equipment, EPA says the trigger leak rate for a 12-month period is 35 percent of the full charge. According to the latest rule, there are two acceptable methods for calculating leak rate:

However, the equipment owner must select and consistently use only one method over the lifetime of all the appliances located at a facility.

Anchor
Annualizing
Annualizing
Annualized Method

Check the formula below to see how leak rates are calculated when you use the annualized calculation method:

Annualized Method Formula


Info

Number of days between refrigerant additions — the number of days that have passed since the last time the refrigerant was added to the system. The maximum number of days that you can use is 365. If there were no additions in the past except for the initial charge addition, the system counts the number of days that passed since the initial charge.

Anchor
Rollingaverage
Rollingaverage
Rolling Average

Check the formula below to see how leak rates are calculated when you use the rolling average calculation method:

Rolling average formula

Whenever the leak rate meets or exceeds the leak rate threshold you set for each refrigerant use purpose (Commercial Refrigeration, Industrial Refrigeration, Air Conditioning, or All Other Appliances), the system generates a leak record, also known as leak event. Learn more about Refrigerant Leak Events.

Anchor
Unitsofmeasure
Unitsofmeasure
Units of Measure

These options provide greater flexibility and compatibility to existing systems. It is possible to choose between three different units of measurement when tracking refrigerants:

  • Pounds and decimals
  • Pounds and ounces
  • Kilograms and grams


Info

The option chosen is for all assets.


Note

Contact your CSM representative if you want to track refrigerant usage in kilograms and grams. 

Anchor
GenerateLeakInspection
GenerateLeakInspection
Generate Leak Inspection

Able to select whether all types of refrigerant assets to be inspected or select specific ODS (ozone depleted substance) type refrigerant assets.

Anchor
Minthresannualandquarterly
Minthresannualandquarterly
Minimum Threshold Annual and Quarterly Leak Inspection

If refrigerant is leaked based on various set trigger rates or exceeds the minimum thresholds, you must go back and inspect that asset. You can set the threshold based on a quarterly or yearly review based on the amount of refrigerant the asset holds. 

EquipmentFull ChargeNumber of Leak Inspections
Commercial Refrigeration and Industrial Refrigeration500 Pounds or moreOnce every 3 months 
Commercial Refrigeration and Industrial Refrigeration50 to 500 PoundsOnce per calendar year 
Comfort Cooling 50 Pounds or moreOnce per calendar year


Info
  1. Commercial Refrigeration can stop leak inspections if calculations of the leak rate doesn't go over 20% for 4 quarters in a row. 
  2. Industrial Refrigeration can stop leak inspections if calculations of the leak rate doesn't go over 30% for 4 quarters in a row. 
  3. Comfort Cooling can stop leak inspections if calculations of the leak rate doesn't go over 10% for one year. 


Anchor
LeakInspectionCategory
LeakInspectionCategory
Leak Inspection Category

Selecting the specific category when Planned Maintenance refrigerant asset work orders are generated.

Anchor
PMpriority
PMpriority
Refrigeration PM Priority

The Refrigeration PM Priority sets the priority assigned to all automatically generated Leak Inspection and Leak Detector Planned Maintenance Work Orders. Whenever a refrigerated asset has been repaired following a leak event, subsequent follow-up inspections are required to ensure the leak has been adequately repaired. The number of inspections required is dependent on the amount of refrigerant the asset holds. By setting all follow-up leak inspection work orders to the Refrigeration PM Priority, you will have an additional tool for monitoring your refrigerated assets. By default, the Refrigeration PM Priority is set to PM Leak Inspection.

Anchor
RefrigerantTrackingProvider
RefrigerantTrackingProvider
Refrigerant Tracking Provider

Which specific provider is going to be used for the Planned Maintenance refrigerant work orders.

Anchor
CARB
CARB
CARB Report

Subscribers who operate refrigerated assets in the state of California are required to submit an annual report. The CARB Report is automatically generated from information contained within ServiceChannel. By selecting the Run CARB Report checkbox, the report will run once the user triggers the report from the Asset Manager module. Before running the CARB report, users must identify which assets are to be included in the report. This is done in the Asset Manager module. See CARB Reporting for more information.

Anchor
PMLeakInspectionNTE
PMLeakInspectionNTE
PM Leak Inspection NTE

The PM Leak Inspection NTE sets the maximum rate that can be charged for an inspection of this type. When an administrator sets this rate, it is applied to all future PM leak inspections. 

Anchor
RefrigerantTrackedBy
RefrigerantTrackedBy
Refrigerant Tracked By

Where refrigerant needs to be tracked. There could be X number of locations that only need to track refrigerant or all locations can be tracked. 

Anchor
PMAdvanceTime
PMAdvanceTime
PM Advance Time

How many days prior to service should a Planned Maintenance work order is generated.

Anchor
Followupworkorder
Followupworkorder
Follow-Up Work Order

You can specify whether a follow-up work order should be automatically created after the original service request is completed with the associated leak record left open.

Once a work order is moved to the Completed status while the associated leak record stays open, a follow-up request gets created and dispatched to the provider so that they can repair the leak and close the leak record. In the meantime, the provider can invoice the original service request.

Selecting this option ensures that no follow-ups get generated. Providers should first close leak records associated with work orders to be able to invoice them. When providers check out of a work order with a leak record left open and specify that they completed the requested service, the work order moves to the Completed / Open Leak Record status. The status signals that providers should go back to this work order to enter all the required leak record information before they can submit an invoice. With an open leak record, the work order cannot be moved to the Completed, Completed / Confirmed, or Completed / Pending Confirmation status. After the leak record is completed, the work order status changes to Completed / Pending Confirmation.

Note

You need to create a new Completed/Open Leak Record status in your admin settings. 

Anchor
Refrigeranttrackingbylocation
Refrigeranttrackingbylocation
Refrigerant Tracking by Location

You can decide whether refrigerant tracking should happen across all your locations or only at those where it’s required.

  • For specific locations: Should you want to track refrigerant usage only at the locations where you have assets containing ozone-depleting refrigerants, the ServiceChannel team can activate refrigerant tracking only for these locations.
  • For locations where there is no equipment with substances that are required to be tracked, the refrigerant tracking process can be deactivated. Turning off refrigerant tracking for a location implies that providers are not prompted to record information on refrigerants they use while servicing refrigeration or HVAC assets at the location.
  • For all locations. You may need to track refrigerant usage across all your locations regardless of refrigerant types and quantities contained in assets at these locations. 

Once the ServiceChannel team configures this for you, the Refrigerant Leak Settings page displays locations the refrigerant tracking process is on.

Note

Contact your CSM representative to add more locations, exclude a location, or make any other changes. 

Anchor
OpenLeakNotification
OpenLeakNotification
Open Leak Notification

  • Charge: Who receives notifications about the open leak receipt.
  • Certification: Which certified provider receives notification about open leak receipt. 
  • Number of Days: How many days before receiving the next notification about open leaks events.

Anchor
SystemCharge
SystemCharge
System Charge

When the entire system exceeds, you can send out a notification. 


Panel
bgColor#F9F9F9
titleColor#0e3367
titleBGColor#EAEAEA
borderStylenone
title⦿ How to Adjust Refrigerant Requirements
  1. Click the pencil icon in the upper right-hand corner to edit the refrigerant requirement Info: Hover the mouse over the information icon to learn more about each individual setting.
    Settings definition info icon
  2. Add EPA Compliance Threshold lbs.
  3. Add Commercial Refrigeration percentage.
  4. Add Industrial Refrigeration percentage. 
  5. Use the drop-down arrow to select follow-up work order for open leak or never. 
  6. Add Air Conditioning percentage. 
  7. Add all Other Appliances percentage.
    Steps 2 thru 7
  8. Use the drop-down arrow to select Calculation Method.
  9. Add Yearly and Quarterly Minimum Threshold Annual and Quarterly Leak Inspections.
  10. Use the drop-down arrow to select Unit of Measure.
  11. Use the drop-down arrow to select Inventory Location.
  12. Use the drop-down arrow to to select Refrigerant PM Priority.
  13. Use the drop-down arrow to select EPA Leak Inspection Category.
  14. Add PM Leak Inspection NTE.
  15. Use the drop-down arrow to select Refrigerant Tracking Provider.
  16. Add Leak Inspection PM generation Advance Timeframe.
  17. Use the drop-down arrow to select Refrigerant Tracked By.
  18. Use the drop-down arrow to select Generate Leak Inspection.
    Steps 8 thru 18
  19. Select or unselect the checkbox to run CARD Report.
  20. Add Open Leak Notification
    1. Charge exceeded recipients.
    2. Certification exception recipients.
    3. Number of Days Between Notifications. 
  21. Select or unselect the checkbox for System Charge Exceeded Notifications
  22. Select or unselect CARD Inspections
    1. Add Calendar State Date
      Steps 19 thru 22
  23. Click the Save button to finalize the settings. 


Tip

It is necessary to complete each step to ensure accuracy for Refrigerant Leak Settings. 

Anchor
AdjustingRefrigerantLeakSetting
AdjustingRefrigerantLeakSetting
Adjusting Refrigerant Leak Setting

After finalizing the settings, you can make adjustments at any point in time. The easy and simple access allows for instance changes whenever there is a need and for keeping all refrigerant assets in compliance. 

Panel
bgColor#F9F9F9
titleColor#0e3367
titleBGColor#EAEAEA
borderStylenone
title⦿ How to Add Adjust Refrigerant Leak Setting
  1. Click the pencil icon on the upper right hand side to edit the settings.
    Adjust Refrigerant Leak Settings Pencil Icon
  2. Make any or all change(s) to the settings.
  3. Click the Save button to finalize the change(s). 

Anchor
ComplianceAcknowledgement
ComplianceAcknowledgement
 Compliance Acknowledgement Statement


While closing a leak inspection work order during the check-out process on a Planned Maintenance work order with at least one refrigerant asset, you can choose to add a requirement to select the leak inspection method used. There can be more than one method selected. In addition, the ability to add an acknowledge statement for users in Provider & Service Automation and SC Provider Mobile to confirm the leak inspection method. You can select at least one or all three platforms.

Panel
bgColor#F9F9F9
titleColor#0e3367
titleBGColor#EAEAEA
borderStylenone
title⦿ How to Add Compliance Acknowledgement Statement
  1. Click the pencil icon on the upper right hand side to edit the settings.
  2. Click the checkbox to include the message for a specific platform(s).
  3. Add your specific statement(s) into each box. 
  4. Click Save to include the statement(s)

    Info

    255 is the maximum number of characters for each statement box. 



Live Search
spaceKeySCU
additionalpage excerpt
placeholderSearch our Knowledge Base
typepage

Panel
titleColor#ffffff
titleBGColor#5fa7d0
borderStylegroove
titleIn this Article

Table of Contents
maxLevel3
minLevel2
indent20px

Panel
titleColorwhite
titleBGColor#75a346
titleRelated Articles

Filter by label (Content by label)
showLabelsfalse
max8
showSpacefalse
sorttitle
cqllabel in ( "refrigerantadmin" , "refrigeranttracking" ) and space = currentSpace ( )